HVAC licensing exam questions
EMS hvac practice exam
EMS Practice HVAC Licensing Exam
References used to create this practice test: International Mechanical Code,
International Fuel Gas Code, Manual J, Manual D and NASCLS’s “Contractors’s Guide to
Business and Project Management”
Answers are at the last pages of this test
1. A tracer wire buried with plastic gas piping shall be minimum ___AWG
a.16
b. 14
c. 18
d. 20
2. The minimum ventilation rate for living area of a residence is the greater of 15 cfm
per person or ____ air changes per hour
A .5
B .35
c.40
d1
3 When using a test pressure of 10 psig, the test gauge shall not be capable of reading
pressures greater than_____PSIG
a. 100
b. 80
c. 50
d. 75
4. The use of gypsum boards to for plenums shall be limited to systems where the
temperature does not exceed _______ degrees F and the temperature of the
conveyed air is kept above the dew point
a. 125
b.110
c250
d.95
5. A sauna room shall have a vent opening above the door at least 4 inches by ____
inches
a. 6
b. 12
c. 10
d. 8
6. Gas piping shall be labeled at intervals not exceeding ______ feet
a. 8
b. 5
c. 4
d. 3
7. A JOINT OBTAINED BY THE JOINING OF METAL PARTS WITH METALLIC MIXTURES OF
ALLOYS WHICH MELT AT 1000 DEGREES F, IS CALLED A __________ JOINT.
a. WELDED
b. MECHANICAL
c. BRAZED
d. SOLDERED
8, If an 6″ X 10″ duct is terminated with a metal louver (75% free area), the louver must be
a minimum _____ square inches
a. 90
b. 60
c. 120
d. 80
9. THE DISTANCE FROM A METER TO A NATRUAL GAS WATER HEATER (40,000 BTUH)
IS 30 FEET. 20 FEET FURTHER DOWN THE LINE IS A FURNACE (120,000
BTUH). WHAT IS THE MINIMUM PIPE SIZE THAT MUST BE USED BETWEEN THE
WATER HEATER AND FURNACE? (PRESSURE LESS THAN 2 LBS, PRESSURE DROP =
.05)?
a) 1/2″
b) 3/4″
c) 1″
d) 3/8″
10. Unless otherwise specified by the manufacturer, vents shall terminate not less than
______feet above the highest connected appliance
a. 12
b. 10
c. 8
d. 5
11. When obtaining outdoor combustion air for an 80,000 btuh appliance from two
horizontal ducts, the free area of each duct must be minimum ______ square inches.
a. 144
b. 27
c. 40
d. 80
12. A type I hood, 5 foot long, wall mounted canopy, serving medium-duty appliances
shall have a minimum capacity of _____ CFM
a. 1000
b. 2500
c. 500
d. 1500
13. Downdraft kitchen exhaust ducts may be constructed of______.
a. all the above
b. sheet metal
c. aluminum
d. PVC
14. When combustion air is mechanically forced into a room, containing appliances
totaling 140,000 BTHU input, the minimum forced CFM shall be ____?
a. 49
b. 140
c. 70
d. 7
15. The maximum cfm of duct leakage allowed with a air handler in place for a 1500
square foot home with .1 inch w.c. is____.
a. 75
b. 150
c. 60
d. 80
16. . A contractor, working on a 15% profit, is calculating a bid price on a project where
the material and labor cost is $1875. The company overhead is 20%. What should
the bid be? $_______
a) $2531.25
b) $2884.61
c) $2367.54
d) $2250.00
17. Omitted
18. For other than appliances installed in fireplaces, a gas shutoA valve shall be located
within ___feet of the appliance
a) 3
b) 4
c) 10
d) 6
19. Appliance pits greater than 12 inches deep shall be lined with masonry extending
___inches above the adjoining grade
a) 4
b) 2
c) 3
d) 6
20. Gas piping may be joined in concealed locations using which of the following
methods?
a) brazing
b) compression fittings
c) unions
d) swing joints
21. 1/2″ copper tubing must be supported a minimum of _______ feet when installed
horizontally
a) 4
b) 10
c) 8
d) 6
22. Equipment, appliances or material included in a list published by a nationally
recognized testing laboratory concerned with product evaluation and states that the
above item meets recognized standards is said to be _____________
a) approved
b) listed
c) certified
d) tested
23. A type I hood is not required for _______>
a) griddles
b) hot dog cookers
c) fryers
d) broilers
24. REFRIGERANTS REMOVED FROM A SYSTEM IN ANY CONDITION WITHOUT
NECESSARILY TESTING OR PROCESSING THEM ARE CALLED___________.
a) RECYCLED REFRIGERANTS
b) RECIEVED REFRIGERANTS
c) RECOVERED REFRIGERANTS
d. RECLAIMED REFRIGERANTS
25. THE MAXIMUM ALLOWABLE HORIZONTAL LENGTH OF A CATEGORY I APPLIANCE
SINGLE WALL VENT CONNECTOR IS _______% OF THE HEIGHT OF THE VENT
a) 50
b) 25
c) 75
d) 100
26. A commercial stainless steel duct must be constructed of ______ gage thickness
a) 20
b) 14
c) 18
d) 16
27. A NON LOAD BEARING STUD MAY BE NOTCHED ______% OF ITS DEPTH.
a) 30
b) 40
c) 25
d) 15
28. CATEGORY I GAS EQUIPMENT MAY BE VENTED WITH WHICH OF THE FOLLOWING
TYPES OF VENTS?
a) ALL THE ABOVE
b) CHIMNEY WITH CLAY LINER
c) TYPE B
d) SINGLE WALL METAL
29. RECLAIMED REFRIGERANTS SHALL NOT BE REUSED IN A DIFFERENT OWNERS
EQUIPMENT UNLESS TESTED AND FOUND TO MEET THE PURITY REQUIREMENTS
OF
a) ARI 700
b) ASTM A53
c) NFPA 54
d) ASHRAE 34
30. IF A GALLON OF OIL CONTAINING 140,000 BTU’S SELLS FOR $1.25, HOW MUCH
WILL 1,000,000 BTU’S COST WHEN USED IN AN 80% AFUE OIL FURNACE
a) $8.93
b) $11.16
c) $14.00
d) $12.78
31. For 3/4 inch steel gas pipe hangers or supports shall be spaced not farther than
_____feet apart
a) 10
b) 4
c) 8
d) 6
32. An auxiliary drain pan must have a minimum depth of ____ inche/s
a) 1.5
b) 1
c) 1.25
d) 2
33.
RECTANGULAR EQUIVALENT OF
a) 16 X 8
A 12″ ROUND DUCT HAS A
b) 15 X 8
c. 14 X 8
d) 17 X 8
34. GAS APPLIANCE CONNECTORS SHALL NOT PASS THROUGH ANY OF THE
FOLLOWING EXCEPT
a) WALLS
b) APPLIANCE HOUSINGS
c) FACTORY BUILT FIREPLACES
d) FLOORS
35. Sauna heaters shall have a thermostat that limits the room temperature to _______
degrees F
a) 194
b) 144
c) 114
d) 120
36. The minimum R value of duct insulation installed in areas other than the
conditioned space or attics is _________
a) R 5
b) R 6
c) R 8
d) R 4
37. ___________ piping may only be used for gas piping outside and underground.
a) Aluminum
b) Copper
c) Steel
d) Plastic
38. The maximum length allowed for a 4 inch dryer duct with two 90 degree bends is
______ feet
a) 25
b) 35
c) 30
d) 40
39. omitted
40. A location that cannot be accessed without damaging permanent parts of a building
is called a/an _____ location
a) inaccessible
b) assessible
c) concealed
d) ready access
41. AN APPLIANCE RATED AT 75,000 BTUH INPUT MUST BE PLACED IN A ROOM
CONTAINING A MINIMUM ______ CUBIC FEET, IF IT DOES NOT RECEIVE
COMBUSTION AIR FROM OUTDOORS. (Use standard method)
a) 3750
b) 7500
c) 1500
d) 75000
42. omitted
43. The ignition source of an appliance shall be elevated not less than _____ unless it is
listed as flammable ignition resistant
a) 6 feet
b) 18 inches
c) 4 feet
d) 24 inches
44. Transition ducts used to connect commercial dryers to exhaust duct shall be limited
to ___ feet in length
a) 4
b) 3
c) 6
d) 8
45. A label shall be aAixed to a gas appliance with all the following information except
_______.
a) BTUH rating
b) manufacture date
c) type of fuel used
d) minimum clearances
46. The miminum size supply line to an oil furnace shall be _______ inch.
a) 1/8
b) 1/16
c) 3/8
d) 1/4
47. A BLOWER WITH AN EXTERNAL STATIC PRESSURE OF .55″ WC IS CONNECTED TO A
70 FT. LONG DUCT. THE SYSTEM INCLUDES (WITH CORESPONDING PRESSURE
DROPS) REGISTERS AND GRILLS (.03″ WC EACH), A COOLING COIL (.15″ WC) AND
FILTER (.10″ WC). WHAT IS THE TOTAL AVAILABLE STATIC PRESSURE REMAINING
FOR SIZING THE DUCT?
a) .15″ WC
b) .17″ WC
c) .30″ WC
d) .24″ WC
48. WHAT IS THE VELOCITY OF 1400 CFM OF AIR IN A DUCT MEASURING 12″ X 30″?
a) 467 FPM
b) 560 FPM
c) 3.8 FPM
d) 360 FPM
49. A system desIgned to shut oA the gas supply to the burners if the oxygen in the
surrounding atmosphere is reduced to a predetermined level is called a ___________
a) carbon dioxide detector
b) oxygen depletion shutoA system
c) automatic shut of valve
d) air regulator system
50. A 75,000 BTUH (INPUT RATING) 80% AFUE FURNACE HAS A TEMPERATURE RISE OF
45-DEGREES. WHAT IS THE CFM?
a) 1667
b) 1212
c) 1515
d) 1175
51. Appliances installed on roofs greater than ______ feet high must have a permanent
means of access.
a) 18
b) 20
c) 16
d) 24
52. A fire damper install at a 2 hour fire rated wall shall have a minimum rating of
_______ hours
a) 2
b) 1.5
c) 3
d) 1
53. Shield plates placed on studs to protect gas piping shall extend _____ inches to each
side of the stud.
a) 1.5
b) 3
c) 4
d) 2
54. The minimum diameter of a close dryer duct shall be ______ inches
a) 6
b) 5
c) 3
d) 4
55. A location that cannot be accessed without damaging permanent parts of a building
is called a/an _____ location
a) concealed
b) assessable
c) inaccessible
d) ready access
56. Screens used to protect intake openings for ventilation may not have a mesh less
than____ inch.
a) 1/16
b) 1/2
c) 1/8
d) 1/4
57. THE MINIMUM INSULATION R-VALUE FOR REFRIGERANT LINES FOR A RESIDENCE
IS ____.
a) R-3
b) R-2
c) 5-5
d) R-4
58. Close dryers exhausting more than ____ cfm must be provided with make up air
a) 150
b) 100
c) 200
d) 75
59. Which of the follow shall not share a type I hood
a) charcoal grille
b) griddle
c) deep fat fryer
d) pzza oven
60. Underfloor access must be a minimum 22 inches high by _______ inches wide
a) 30
b) 24
c) 28
d) 36
61. Closets containing close dryers must have a make up air opening not less than ____
square inches
a) 75
b) 100
c) 150
d) 50
62. Grease ducts in enclosures shall have a clearance of ________ inches to
construction of non combustible gypsum attached to non combustible structures
a) 18
b) 12
c) 6
d) 3
63. Which of the following heating systems must have its eAiciency posted on a
certificate placed on or inside the electrical distribution panel of new residential
construction
a) Electric baseboard
b) unvented room heater
c) gas furnace
d) electric furnace
64. A ventilation system in a 20,000 square foot enclosed parking garage shall be
capable of producing a minimum of _____ cfm, while full-on.
a) 10,000
b) 20,000
c) 5000
d) 15,000
65. IN ORDER TO SUPPLY OUTDOOR COMBUSTION AIR USING THE TWO OPENING
METHOD WITH HORIZONTAL DUCTS, WHAT DUCT SIZE BELOW WOULD BE THE
MINIMUM NEEDED TO HANDLE A 140,000 BTUH FURNACE
a) 3.5″ X 10″
b) 8.5″ X 10″
c) 7″ X 10″
d) 14′ X 10″
66. Factory built fireplaces must be listed and labeled according to __________.
a) UL 348
b) UL127
c) UL 187
d) UL 124
67. A single wall oil heat chimney connector shall have ______ clearance from
combustibles
a) 9”
b) 18”
c) 36”
d) 12”
68. A plastic condensate pan must have a minimum thickness of ______ inch
a) .0250
b) .0625
c) .0375
d) .0276
69. If natural ventilation is used, a building, measuring 3000 square feet, must have a
minimum openable area of ______ square feet.
a) 120
b) 150
c) 300
d) 450
70. Duct smoke detectors shall comply with______.
a) UL 268
b) UL 181
c) ASTM 34
d) NFPA 72
71. A 2 inch diameter gas pipe must be purged with an inert gas before opening if it is
greater than _____feet long.
a) all of the above
b) 30
c) 50
d) 40
72. Unless protected by approved area smoke detectors, smoke detectosrs are required
in the return air duct or plenum on any system with a design capacity greater than
_______cfm.
a) 1500
b) 2000
c) 4000
d) 3000
73. IF A CONTRACTOR WORKS ON 15% PROFIT, WHAT WOULD HIS SALES HAVE TO BE
TO MAKE $75,000?
a) $600,000
b) $112,000
c) $500,000
d) $862,500
74. A single wall low heat 6 inch diameter chimney connecter shall have a minimum
thickness of ______
a) 22
b) 16
c) 26
d) 24
75. The verical distance between the front lower lip of a type I or II hood and the surface
of the appliance shall not extend more than ______ feet
a) 3.6
b) 4
c) 2
d) 3
76. Vented wall furnaces shall be located so that a door cannot swing within _____
inches of the air inlets or outlets of such furnace measures at right angles to the
openings
a) 12
b) 18
c) 36
d) 24
77. GAS LOGS THAT USE INDOOR AIR FOR COMBUSTION SHALL NOT BE LOCATED IN
_______.
a) BASEMENTS
b) BEDROOMS
c) LIVING ROOMS
d) KITCHENS
78. THE VELOCITY OF 250 CFM OF AIR IN A FLEXIBLE, SPIRAL WIRE HELIX CORE DUCT
SIZED AT .08″ WC STATIC PRESSURE IS ______.
a) 500 FPM
b) 900 FPM
c) 400 FPM
d) 750 FPM
79. Which of the following is not required for a heat pump installation
a) load calculation
b) programmable thermostat
c) a permit
d) a means of controlling electric resistance heat from operating when the heat
pump can handle the load
80. Exhaust outlets that terminate above a roof shall have a discharge outlet not less
than ___ inches above the roof surface
a) 36
b) 30
c) 48
d) 40
81. A CUSTOMER MOVES UP FROM AN 8 SEER TO A 13 SEER AIR CONDITIONER. WHAT
WOULD HIS YEARLY SAVING BE IF HE WAS PAYING $650 PER YEAR FOR AIR
CONDITIONING
a) $197
b) $325
c) $250
d) $260
82. A CEILING HAS A TOTAL U-VALUE OF .07. WHAT IS THE NEW R-VALUE IF R-19 IS
ADDED?
a) 33.28
b) 32.28
c) 30.28
d) 31.28
83. The control side of a floor furnace must have a minimum _____inches clearance
a) 24
b) 18
c) 20
84. ) 12
84. Which of the following must have a flame spread rating no greater than 5 feet when
installed in plenums.
a) pneumatic tubing
b) wiring
c) all the above
85. ) fire sprinkler piping
85. The maximum size unvented gas heater that may be installed in a residential
bathroom measuring 1600 cubic feet is________btuh
a) 8000
b) 4000
c) 3000
d) 6000
86. The total slope of a 24 foot horizontal grease duct must be at least ___ feet
a) .60
b 1.75
c) .40
d) 1.50
87. If a water level detection device is used in an auxiliary drain pan it must conform
to_______.
a) ASTM 243
b) UL 508
c) UL 181
d) ASI 84
88. The vent cap of an oil tank must have a screen mesh no finer than No. _______
a) 10
b) 4
c) 6
d) 8
89. WHAT IS THE DESIGN FRICTION RATE WHEN THE AVAILABLE STATIC PRESSURE
FOR THE DUCT SYSTEMIS .36″ WC AND THE RUN WITH THE LONGEST EFFECTIVE
LENGTH IS 375 FEET?
a) .05″ WC
b) .08″ WC
c) .15″ WC
d) .10″ WC
90. Passageways in attics shall not be less than _____ inches wide
a) 24
b) 20
c) 30
d) 22
91. AN APPLIANCE THAT REQUIRES 18″ CLEARANCE TO COBUSTIBLES ON ITS SIDES,
MAY HAVE ITS CLEARANCE REDUCED TO ______ IF .024″ SHEETMETAL WITH A
VENTILATED AIR SPACE IS USED TO PROTECT THE COMBUSTIBLE SURFACE.
a) 6”
b) MAY NOT HAVE CLEARANCE REDUCED
c) 12”
d) 9”
92. A vertical pipe supplying gas is a________
a) riser
b) leader
c) upright
d) standpipe
93. Copper piping shall not be used if the gas contains more than __ grains of hydrogen
sulfide per 100 standard cubic feet.
a) .3
b) 3
c) .5
d) 6
94. Brazing alloys used on gas piping shall not contain more than_____ percent
phosphorus
a) .005
b) .5
c) 5
d) .05
95. Duct insulation installed within ____inches of a type I hood shall be noncombustible
or be listed for the application
a) 18
b) 6
c) 12
d) 24
96. The minimum distance between the cooking surface and a grease filter serving
burners with flames is _____ feet
a) 1
b) 3.5
c) .5
d) 2
97. The minimum thickness (inches) for a 14 inch round galvanized air duct at 1” wc is
___.
a) .013
b) .016
c) .023
d) ,018
98. FOR A BUILDING TO BE MAINTAINED AT 70 F, HOW MANY BTUH ARE REQUIRED TO
OFFSET 300 CFM OF 20 F OUTDOOR VENTILATION?
a) 16,500
b) 6,600
c) 6,000
d) 1.400
99. The maximum operating pressure of LP gas systems shall not exceed ____ unless
the building or area is constructed according to NFPA 58, Chapter 10
a) 10
b) .5
c) 5
d) 20
100.
THE AMERICANS WITH DISABILITIES ACT APPLIES TO ALL EMPLOYERS WHO
HAVE _______ OR MORE EMPLOYEES
a) 25
b) 15
c) 50
d) 10
101.
Flexible air ducts______.
a) shall not be limited in length
b) shall be limited to 14 feet in length
c) shall be labeled 181-B
d) May convey air at up to 275 degrees
102.
The minimum allowable HSPF rating of an air-cooled residential heat pump is
_________
a) 7.0
b) 8.2
c) 6.8
d) 7.7
103.
A 500 SQUARE FOOT CONFERENCE ROOM REQUIRES _______CFM OF
OUTDOOR VENTILATION
a) 125
b) 250
c) 75
d) 150
104.
When mechanically ventilating a 1500 square foot conference room in an
oAice building, how many CFM of outdoor air are required?
a) 375
b) 1000
c) 50
d) 3000
105.
Access points for inspecting and servicing fire dampers shall be labeled FIRE
DAMPER with letter no less than _____ inch/s high
a) .5
b) .75
c) 2
d) 1
106.
Unless protected from vehicle impact, appliances shall be installed a
minimum ______ feet above the floor of a private garage
a) 6
b) 5
c) 8
d) 9
107.
Cleanouts located on horizontal straight grease ducts shall be placed not
more than ____feet apart
a) 100
b) 15
c) 20
d) 10
108.
Unless otherwise approved, ducts shall not be installed within ____ inches of
earth.
a) 4
b) 3
c) 5
d) 6
109.
109. An employee earns $20/hour On Thanksgiving week, he works 40 hours
and is paid an extra 8 hours for working on Thanksgiving Day. What are his/her gross
wages, before taxes and other deductions?
a) $960
b) $1040
c) $1120
d) $1440
110.
A gas regulator that reduces incoming pressure between .5 and 5 psig to a
lower pressure is called a __________.
a) low pressure regulator
b) service entrance regulator
c) high pressure regulator
d) medium pressure regulator
111.
A HEAT PUMP IN A RESIDENCE MUST BE CONTROLLED BY WHICH OF THE
FOLLOWING?
a) A PROGRAMABLE THERMOSTAT
b) A DEVICE TO PREVENT SUPPLEMENTARY HEAT FROM COMING ON IF HEAT
PUMP CAN HANDLE THE LOAD ALONE
c) A DEVICE THAT ALLOWS SUPPLEMENTARY HEAT OPERATION DURING DEFROST
CYCLES EXCEEDING 15 MINUTES
d) A FOSSIL FUEL KIT
112.
When bending metallic gas pipe, the inside radius shall not be less than
_____ times the diameter
a) 6
b) 10
c) 5
d) 25
113.
THE LARGEST A BORED HOLE MAY BE IN A 2” x 9.5″ joist is
a) 3.14″
b) 3.31″
c) 3″
d) 2.85″
114.
When aluminum foil is used as a vapor retarder for duct insulation it must be
minimum
_____ mils thick
a) 4
b) 2
c) 1
d) 6
115.
A label shall be aAixed to the gas appliance with all the following information
except _______
a) BTUH rating
b) type of fuel used
c) manufacture date
d) minimum clearances
116.
Through the wall exhausted environmental air must be minimum_____ feet
horizontally from mechanical intakes
a) 12
b) 8
c) 3
d) 10
117.
THE MAXIMUM BTUH RATING OF AN UNVENTED GAS HEATER INSTALLED IN
A 15 X 20 ROOM WITH 8 FOOT CEILINGS IS (infiltraion rate is greater than .40 ACH)?
a) 48,000
b) 40,000
c) 2,400
d) 6,000
118.
Liquid adhesive used on air filters shall have a flsh point no lower than ______
degrees F
a) 230
b) 275
c) 250
d) 325
119.
Unless welded or placed in a ventilated shaft, the maximnm operating
pressure of gas piping in a residence shall not exceed _______ psig
a) .5
b) 10
c) 2
d) 5
120.
a) 6
b) 12
c) 10
d) 4
Duct lining shall be interupted _____ inches downstream of a duct heater
121.
TWO NATURALLY VENTILATED APPLIANCES WITH A COMBINED CAPACITY
OF 130,000 BTUH ARE CONNECTED TO A COMMON B-VENT, 18′ HIGH WITH TWO
90-DEGREE ELBOWS. WHAT SIZE COMMON VENT SHOULD BE USED?
a) 5″
b) 7″
c) 4″
d) 6″
122.
a) .087
Shield plates on studs must be a minimum ____ – inch thick
b) .0250
c) .075
d) .0575
123.
A floor furnace shall be placed such that a drapery can be no nearer than
______ to the register of the furnace
a) 18
b) 12
c) 6
d) 8
124.
Corridors are generaly not permitted to be used as return ducts, however the
hallway of a tenant space ______ square feet or less may be used for return air.
a) 1200
b) 500
c) 750
d) 1000
125.
Where holes or notches for gas tubing are less than 1.5 inches from the
nearest edge of a wood stud, they must be protected by metal shields not less than
____inch thick.
a) .250
b) .062
c) .0575
d) .667
126.
The minimum cross-sectional dimension of a combustion air duct shall be
________ inches
a) 3
b) 8
c) 4
d) 6
127.
The highest point of an attic must be at least ___inches in order to be used as
a location for an appliance.
a) 28
b) 30
c) 24
d) 36
128.
A gas line serving a grill may be installed a minimum ______ inches below
ground as long as it is approved and not susceptible to physical damage
a) 8
b) 12
c) 6
d) 16
129.
Which rooftop appliance does not require guardrail protection?
a) one located 3 feet form roof edge
b) one located 6 feet from roof edge
c) one located 9 feet from roof edge
d) one located 11feet from roof edge
130.
When obtaining combustion air from outdoors the intake open must be
minimum _____ inches above grade
a) 6
b) 12
c) 24
d) 8
131.
A HOUSE HAS A HEAT LOSSS OF 48,000 BTUH AT 20-DEGREE OUTDOOR
TEMPERATURE. WHAT IS THE HEAT LOSS AT 40-DEGREE OUTDOOR
TEMPERATURE?
a) 18,000 BTUH
b) 124,000 BTUH
c) 19,200 BTUH
d) 28,800 BTUH
132.
a) 60
b) 36
c) 48
d) 24
133.
Duct insulation shall have the R value printed every_________ inches
A CONTRACTOR PAYS $750 FOR A FURNACE PLUS 7% TAX. WHAT WOULD
HIS SALES PRICE BE IF HE WISHED TO MAKE 30% GROSS PROFIT?
a) $1028
b) $1146
c) $1043
d) $975
134.
A 30′ X 8′ PARTITION (2 X 4 STUDS, GYPSUM ON BOTH SIDES, NO
INSULATION) SEPARATES TWO ROOMS HAVING A TEMPERATURE DIFERENCE OF
20 DEGREES. WHAT IS THE WINTER HEAT LOSS THROUGH THE PARTITION?
a) 3,535 BTUH
b) 15,360 BTUH
c) 1,512 BTUH
d) 2,609 BTUH
135.
Which of the following gas piping materials shall not be used in exterior
locations or underground
a) steel
b) plastic
c) brass
d) aluminum
136.
a) ?
b) ?
137.
This question eliminated
Gas piping installed underground beneath building may not be incased in
_________.
a) cement
b) steel pipe
c) plastic pipe
d) wrought iron conduit
138.
Floor registers must support ______lbs consentrated load on a 2 inch disk
applied at its most critical area
a) 100
b) 250
c) 150
d) 200
139.
AN AIR CONDITIONER HAS HIGH SUCTION AND A LOW HEAD
PRESSURES. WHAT WOULD BE A LIKELY CAUSE?
a) DIRTY CONDENSER COIL
b) DIRTY FILTERS
c) CLOGGED METERING DEVICE
d) BAD OR WEAK COMPRESSOR VALVES
140.
When cutting threads, a 3/4 inch pipe shall have approximately _______
treads cut
a) 12
b) 11
c) 10
d) 13
141.
Type I grease ducts shall have a clearance of _____ inches to combustible
construction
a) 18
b) 3
c) 6
d) 12
142.
Grease ducts shall provide an air velocity not less than _______ feet per
minute
a) 400
b) 750
c) 250
d) 500
143.
IF PROTECTION FROM VEHICLE IMPACT IS NOT PROVIDED, APPLIANCES
INSTALLED IN PRIVATE GARAGES MUST BE INSTALLED _____ FEET ABOVE THE
FLOOR.
a) 7
b) 6
c) 8
d) 5
144.
THE MAXIMUM HORIZONTAL LENGTH OF A SINGLE WALL CONNECTOR IS
______% OF THE HIEGHT OF THE CHIMNEY OR VENT.
a) 50
b) 100
c) 75
d) 150
145.
a) 3/4
b) 1/2
c) 5/8
d) 1
146.
Condensate piping must no be less than _____ inch diameter
The unthreaded portion of a gas piping outlet shall not extend less then
______ through a slab floor
a) 1.5
b) 3
c) 2
d) 1
147.
A DOUBLED UP STUD IN A LOAD BEARING WALL MAY HAVE A HOLE BORED
UP TO ______% OF IT DEPTH
a) 25
b) 40
c) 60
d) 15
148.
A vent is not _____
a) site made
b) a passage way for carrying combustion products
c) factory made
d) listed and labeled
149.
A HOUSE HAS A HEATING LOAD OF 48,000 BTUH. HOW MANY CFM ARE
REQUIRED FOR A ROOM WITH A HEAT LOAD OF 5200 BTUH, USING A FURNACE
WITH A 1200 CFM BLOWER?
a) 468
b) 112
c) 130
d) 1112
150.
A home must be provided with a space heating system capable of maintaing
a minimum indoor temperature of _____ degree at a point 3 feet obove the floor level
on a design heating day
a) 78
b) 70
c) 75
d) 68
151.
An appliance that causes a positive vent pressure and produces excessive
condensation in the vent is a Catagory ______ appliance
a) II
b) IV
c) I
d) III
152.
Pressure sensitve tapes used on flexible ducts shall be lableled as
conforming to ______
a) UL 181 A
b) UL 181-FX
c) UL 181 A-P
d) UL 181 B
153.
THE DISTANCE FROM A METER TO A NATRUAL GAS WATER HEATER (40,000
BTUH) IS 30 FEET. 20 FEET FURTHER DOWN THE LINE IS A GAS FURNACE (120,000
BTUH). WHAT IS THE MINIMUM PIPE SIZE THAT MUST BE USED BETWEEN THE
WATER HEATER AND FURNACE? (PRESSURE LESS THAN 2 LBS, PRESSURE DROP =
.05)?
a) 1/2″
b) 3/4″
c) 1″
d) 3/8″
Answers
1. c 404.Tracer IFGC (Note, The 2024 IFGC has changed from 18 awg to 14 awg)
2. b Table 403.3.1.1 IMC private dwellings, living areas
3. c section 406.4 IFGC (5 x test pressure)
4. a section 602.2 IFGC
5. d section 914.5 IMC
6. b section 401.5 IFGC
7. c Chapter 2 Definition of brazed
8. d section 304.10 IFGC ( 6 x10 = 60 sq. in., 60/.75 = 80 sq. in.)
9. b See “longest length method” in gas code appendix
10. d section 802.6 imc
11. d section 304.6.1 IFGC 80,000 btuh/2000 btuh = 40 square inches
12. d section 507.5.3 imc (300 X 5 ft = 1500 cfm)
13. a section 505 ( exception includes PVC in some cases
14. a section 304.9 gas code
15. c section R403 energy code, 4 cfm per 100 sq. ft.
1500 sq. ft. / 100 = 15
15 x 4 =60 cfm
16. b. contractor must make 35% to cover both overhead (20%) and profit (15%).
Saies price = cost / 100% – (% OH and profit)
= 1875 / (1.00 -.35)
= 1875 / .65
= $2884.61
17. c 411.1 gas code
18. d 409 gas code IFGC
19. a section 303.7 IMC
20. a 404.5 gas code
21. d Table 305.4 IMC
22. b definitions-listed
23. b section 507 IMC, hot dog cooker does not emit grease laden vapor
24. c Chapter 2 definition “recovered refrigerant” mech code
25. c SECTION 803.10.2 IMC LENGTH OF VENT CONNECTOR, GAS CODE