                   Based on 2018 and 2021 IMC and IFGC

  1. A tracer wire buried with plastic gas piping shall be minimum ___AWG.
    1. 16
    2. 14
    3. 18
    4. 20
  1. The minimum ventilation rate for living area of a residence is the greater of 15 cfm per person or ____ air changes per hour.
    1. .5
    2. .35
    3. .40
    4. 1
  1. When using a test pressure of 10 psig, the test gauge shall not be capable of reading pressures greater than_____PSIG .
    1. 100
    2. 80
    3. 50
    4. 75
  1. The use of gypsum boards to for plenums shall be limited to systems where the temperature does not exceed _______ degrees F and the temperature of the conveyed air is kept above the dew point.
    1. 125
    2. 110
    3. 250
    4. 95
  1. A sauna room shall have a vent opening above the door at least 4 inches by ____ inches.
    1. 6
    2. 12
    3. 10
    4. 8
    5.  
  2. A house with indoor temperature of 70F located in an area with a 10F outdoor design temperature has a heat loss of 48,000 BTUH. What is the heat loss at 40 F outdoor design temperature?
  3. a.  40,000 BTUH
  4. b   28,000 BTUH
  5.  c  24,000 BTUH
  6. d  36,000 BTUH
  1. Gas piping shall be labeled at intervals not exceeding ______ feet.
  2. a) 8
    1. 5
    2. 4
    3. 3
  1. A JOINT OBTAINED BY THE JOINING OF METAL PARTS WITH METALLIC MIXTURES OF ALLOYS WHICH MELT AT 1050 DEGREES F, IS CALLED A __________ JOINT.
    1. WELDED  
    2. MECHANICAL
    3. BRAZED
    4. SOLDERED
  1. If an 6″ X 10″ duct is terminated with a metal louver (75% free area), the louver must be a minimum _____ square inches.
    1. 90
    2. 60
    3. 120
    4. 80
  1. A gas regulator that reduces incoming pressure between .5 and 5 psig to a lower pressure is called a __________.
    1. service entrance regulator
    2. low pressure regulator
    3. high pressure regulator
    4. medium pressure regulator
  1. Unless otherwise specified by the manufacturer, vents shall terminate not less than ______feet above the highest connected appliance.
    1. 12
    2. 10
    3. 8
    4. 5
  1. When obtaining combustion air from a crawl space, the free area of the crawl space vent to the outside must be a minimum ________ the size of the combustion air opening.
    1. 4 times
    2. 5 times
    3. 3 times
    4. 2 times
  1. A type I hood, 5 foot long, wall mounted canopy, serving medium-duty appliances shall have a minimum capacity of _____ CFM.
    1. 1000
    2. 2500
    3. 500
    4. 1500
  1. Downdraft kitchen exhaust ducts may be constructed of______.
    1. all of the above
    2. sheet metal
    3. aluminum
    4. PVC
  1. When combustion air is mechanically forced into a room, a minimum rate of ______ cfm per 1000 btu/h of combined input rating of all installed appliances must be supplied.
    1. .35
    2. 0
    3. .25
    4. .40
  1. The maximum cfm of duct leakage allowed with a air handler in place for a 1500 square foot home with .1 inch w.c. is____.
    1. 75
    2. 150
    3. 60
    4. 80
  1. Plastic pipe shall not be operated at pressures greater than ______ psig for LP gas
    1. 100
    2. 15
    3. 30
    4. 10
  1. Semi-ridgid metallic tubing used as appliance connectors shall not exceed ___ feet
    1. 8
    2. 3
    3. 6
    4. 5
  1. For other than appliances installed in fireplaces, a gas shutoff valve shall be located within ___feet of the appliance
    1. 3
    2. 4
    3. 10
    4. 6
  1. Appliance pits greater than 12 inches deep shall be lined with masonry extending ___inches above the adjoining grade
    1. 4
    2. 2
    3. 3
    4. 6
  1. Gas piping may be joined in concealed locations using which of the following methods?
    1. brazing
    2. compression fittings
    3. unions
    4. d) swing joints
  1. 1/2″ copper tubing must be supported a minimum of _______ feet when installed horizontally.
    1. 4
    2. 10
    3. 8
    4. 12
  1. Equipment, appliances or material included in a list published by a nationally recognized testing laboratory concerned with product evaluation and states that the above item meets recognized standards is said to be _____________ .
    1. approved
    2. listed
    3. certified
    4. tested
  1. A type I hood is not required for _______.
    1. griddles
    2. hot dog cookers
    3. fryers
    4. broilers
  1. REFRIGERANTS REMOVED FROM A SYSTEM IN ANY CONDITION WITHOUT NECESSARILY TESTING OR PROCESSING THEM ARE CALLED___________.
    1. RECYCLED REFRIGERANTS
    2. RECIEVED REFRIGERANTS
    3. RECOVERED REFRIGERANTS
    4. RECLAIMED REFRIGERANTS
  1. THE MAXIMUM ALLOWABLE HORIZONTAL LENGTH OF A CATEGORY I APPLIANCE SINGLE WALL VENT CONNECTOR IS _______% OF THE HEIGHT OF THE VENT
    1. 50
    2. 25
    3. 75
    4. 100
  1. A commercial stainless steel grease duct must be constructed of ______ gage thickness
    1. 20
    2. 14
    3. 18
    4. 16
  1. A NON LOAD BEARING STUD MAY BE NOTCHED ______% OF ITS
    1. 30
    2. 40
    3. 25
    4. 15
  1. CATEGORY I GAS EQUIPMENT MAY BE VENTED WITH WHICH OF THE FOLLOWING TYPES OF VENTS?
    1. ALL THE ABOVE
    2. CHIMNEY WITH CLAY LINER
    3. TYPE B
    4. SINGLE WALL METAL
  1. RECLAIMED REFRIGERANTS SHALL NOT BE REUSED IN A DIFFERENT

OWNERS EQUIPMENT UNLESS TESTED AND FOUND TO MEET THE PURITY

REQUIREMENTS OF

  1. ARI 700
  2. ASTM A53
  3. NFPA 54
  4. ASHRAE 34
  1. IF A GALLON OF OIL CONTAINING 140,000 BTU’S SELLS FOR $1.25,

HOW MUCH WILL 1,000,000 BTU’S COST WHEN USED IN AN 80% AFUE OIL

FURNACE

  1. $8.93
  2. $11.16
  3. $14.00
  4. $12.78
  1. For 3/4 inch steel gas pipe hangers or supports shall be spaced not farther than _____feet apart
    1. 10
    2. 4
    3. 8
    4. 6
  1. An auxiliary drain pan must have a minimum depth of ____ inche/s
  2. a) 1.5
    1. 1
    2. 25
    3. 2
  1. A 12″ ROUND DUCT HAS A RECTANGULAR EQUIVALENT OF
    1. 16 X 8
    2. 15 X 8
    3. 14 X 8
    4. 17 X 8
  1. GAS APPLIANCE CONNECTORS SHALL NOT PASS THROUGH ANY OF THE FOLLOWING EXCEPT
    1. WALLS
    2. APPLIANCE HOUSINGS
    3. FACTORY BUILT FIREPLACES
    4. FLOORS
  1. Sauna heaters shall have a thermostat that limits the room temperature to _______ degrees F
    1. 194
    2. 144
    3. 114
    4. 120
  1. The minimum R value of duct insulation installed in areas other than the conditioned space or attics is _________
    1. R 5
    2. R 6
    3. R 8
    4. R 4
  1. ___________ piping may only be used for gas piping outside and underground.
    1. Aluminum
    2. Copper
    3. Steel
    4. Plastic
  1. The maximum length allowed for a 4 inch dryer duct with two 90 degree bends is ______ feet
    1. 25
    2. 35
    3. 30
    4. 40
  1. The minimum return opening to an 80,000 btuh (output rating) forced air furnace shall be _____ square inches.
    1. 160
    2. 80
    3. 140
    4. 100
  1. A location that cannot be accessed without damageing permanent parts of a building is called a/an _____ location
    1. inaccessible
    2. assessible
    3. concealed
    4. ready access
  1. AN APPLIANCE RATED AT 75,000 BTUH INPUT MUST BE PLACED IN A ROOM CONTAINING A MINIMUM ______ CUBIC FEET WITHOUT THE INTRODUCTION OF OUTDOOR COMBUSTION AIR.
    1. 3750
    2. 7500
    3. 1500
    4. 75000
  1. A FUEL FIRED FURNACE, MEASURING 22 CUBIC FEET MUST BE

PLACED IN A ROOM GREATER THAN __________ CUBIC FEET IF IT IS NOT

APPROVED FOR CLOSET INSTALATION

  1. 264
  2. 352
  3. 220
  4. 564
  1. he ignition source of an appliance shall be elevated not less than _____ unless it is listed as flammable ignition resistant
    1. 6 feet
    2. 18 inches
    3. 4 feet
    4. 24 inches
  1. Transition ducts used to connect commercial dryers to exhaust duct shall be limited to ___ feet in length
    1. 4
    2. 3
    3. 6
    4. 8
  1. A label shall be affixed to a gas appliance with all the following information except _______
    1. BTUH rating
    2. manufacture date
    3. type of fuel used
    4. minimum clearances
  1. The miminum size supply line to an oil furnace shall be _______ inch.
  2. a) 1/8
    1. 1/16
    2. 3/8
    3. 1/4
  1. A BLOWER WITH AN EXTERNAL STATIC PRESSURE OF .55″ WC IS CONNECTED TO A 70 FT. LONG DUCT. THE SYSTEM INCLUDES

REGISTERS AND GRILLS (.03″ WC EACH), A COOLING COIL (.15″ WC) AND FILTER (.10″ WC). WHAT IS THE TOTAL AVAILABLE STATIC PRESSURE REMAINING FOR SIZING THE DUCT?

  1. .15″ WC
  2. .17″ WC
  3. .30″ WC
  4. .24″ WC
  1. WHAT IS THE VELOCITY OF 1400 CFM OF AIR IN A DUCT MEASURING 12″ X 30″?
    1. 467 FPM
    2. 560 FPM
    3. 8 FPM
    4. 360 FPM
  1. A system designed to shut off the gas supply to the burners if the oxygen in

the surrounding atmosphere is reduced to a predetermined level is called a

___________

  1. carbon dioxide detector
  2. oxygen depletion shutoff system
  3. automatic shut of valve
  4. air regulator system
  1. A 75,000 BTUH (INPUT RATING) 80% AFUE FURNACE HAS A TEMPERATURE RISE OF 45-DEGREES. WHAT IS THE CFM?
    1. 1667
    2. 1212
    3. 1515
    4. 1175